Location: Home >>Product >>Smart Transmission >>Video image monitoring

On line monitoring device for mountain fire prevention of transmission lines

型号:DX-WPS100-SH

Online consulting18926505116


Product details

On line monitoring device for mountain fire prevention of transmission lines

   model:DX-WPS100-SH

1、 Demand analysis

The transmission line forest fire has the characteristics of outburst, randomness of disaster occurrence and huge loss in a short time. Therefore, shortening fire detection time, quickly finding and extinguishing forest fire, and preventing fire from spreading and out of control have become the top priority of fire prevention in transmission line forest areas. The infrared dual spectrum anti mountain fire online monitoring device is an intuitive and effective way to prevent the occurrence of abnormal mountain fire events and eliminate them in the bud. To achieve this, we need to solve the weakness of human eye monitoring. We have developed an infrared dual spectrum mountain fire monitoring and alarm technology, which can be prevented through machine eyes+machine brains, and truly achieve 24-hour effective monitoring to ensure the safe and stable operation of the line.


2、 Working principle

The online monitoring device for mountain fire prevention of transmission line is composed of main control unit, video monitoring unit, infrared dual spectrum mountain fire monitoring unit, laser illuminator, communication unit, power supply unit, mounting bracket and auxiliary materials; The infrared dual spectrum mountain fire monitoring unit can automatically cruise to detect the heat source of the target environment in real time, locate the mountain fire occurrence point, and send the specific location of the mountain fire occurrence point to the power department in the wireless 4G/5G network mode. The command center can display the mountain fire occurrence point through the intuitive PTZ remote adjustment video display on the installed background software, mobile terminals, etc, At the same time, the path planning of GIS geographic information system can be used to direct the rescue team to the scene by short path to complete the rescue work.


3、 Product features

(1) Basic configuration of mountain fire monitoring: main control unit, video monitoring unit, infrared dual spectrum mountain fire monitoring unit, laser illuminator, communication unit, power supply unit, installation bracket and auxiliary materials;

(2) Thermal imaging fire point detection: when a mountain fire is detected, immediately link the video monitoring device to upload the video to the monitoring center platform, and alert relevant personnel for emergency treatment.

(3) WeChat APP alarm function: you can view infrared and visible light images through WeChat and APP.

(4) Real time analysis of panoramic watch: 24h continuous monitoring and real-time analysis of panoramic view, and no omission of hidden mountain fire

(5) Linkage PTZ orientation: in case of danger, PTZ will be immediately awakened and the ball will be automatically controlled to orient the mountain fire;

(6) Automatic zoom detail analysis: the visible light is zoomed in, close and close, and there is nowhere to hide the mountain fire;

(7) Mountain fire coordinate positioning: Beidou and 3D point cloud work together to capture the longitude and latitude of mountain fire;

(8) Alarm input/output interface: It has 4-way alarm input interface and alarm output function. It can not only protect the anti-theft of its own equipment, but also access other alarm quantities.

(9) Effectiveness and accuracy of patrol inspection: to save users from economic and human losses caused by missing and false reports of mountain fire hazards.

(10) Integrated power supply unit: solar energy and lithium battery are used for power supply to ensure sufficient power supply and stability of the system.

(11) It shall have the function of remote modification and setting of equipment IP address;

(12) It shall have 4G/5G/WIFI full network communication capability;


4、 Product parameters

Serial No

category

project

technical parameter

1     

Overall performance

Complete machine configuration

Main control unit, video monitoring unit, infrared mountain fire protection monitoring unit, laser illuminator, communication unit, power supply unit, audible and visual alarm, mounting bracket and auxiliary materials.

2     

Overall quality

Less than 40KG (including solar panel and support)

3     

texture of material

Stainless steel body+hot galvanized support

4     

Video monitoring unit

camera

Industrial video sensor 2 megapixel 1920 (H) X1080 (V)

5     

Optical zoom

30X

6     

With AI identification function

Support front-end AI video recognition function to automatically identify hidden dangers such as mountain fire.

7     

PTZ range

Horizontal 360 ° continuous rotation, vertical+60~- 60 °;

8     

Infrared mountain fire prevention monitoring unit

camera lens

3CAM Opto mechanical Design of Germanium Mirror

9     

chip

Two dimensional array suspended microbolometer array

10    

Imaging resolution

≥384*288

11    

Temperature measurement repeatability

≤±0.5%

12    

Detection radius

≥3km,1-3m2Ignition area

13    

Scan cycle

30 minutes (or self setting)

14    

Laser illuminator

Laser light source

Wavelength: 810nm military grade infrared laser; Illumination angle: 1 °~ 20 °

15    

Laser lens

25 times 0.8~20mm ultrashort zoom, laser 400 μ M section imaging lens; Synchronous zoom matching;

16    

Communication unit

communication mode

All Netcom 4G/5G/WIFI wireless transmission

17    

Data security

VPN dedicated channel can be used for communication with the master station, and encryption transmission is optional.

18    

Access protocol

Access to monitoring platforms of provincial power companies such as Southern Power Grid and State Grid

19    

Power supply unit

Battery capacity

100Ah/12V,Lithium iron phosphate battery High reliability battery

20       

Solar panel power

360W/18V,Single crystal silicon high-efficiency solar panel

21       

Power supply duration

The power supply requirement that the device can operate normally for 15 days without continuous illumination.

22       

Other parameters

work environment

Working temperature: - 40~+70 ℃; Relative humidity: 5-99% RH

23    

Overall service life

More than 8 years

24    

Degree of protection

IP66




Contact us

Shenzhen Dingxin Smart Technology Co., Ltd
Tel:0755-21612345 Mobile:18926505116
Fax:0755-21612345 QQ:2986188Mail:dxzhkj@126.com
Address: Room 201, No. 2, Xiangyuer Industrial Park, No. 8, Longsheng Road, Longgang Community, Longgang Street, Longgang District, Shenzhen

The online monitoring, distributed fault location and cable online monitoring equipment for power transmission and distribution lines launched by SHENZHEN DINSEE SMART TECHNOLOGY CO.,LTD. has been widely used in Southern Power Grid and State Grid, and has achieved good results.

Record No.: Yue ICP Bei 2022070794-1 | Website Map XML Map