Location: Home >>Product >>Smart Distribution >>Line monitoring

Distribution line image monitoring device

model:DX-WPS100-HGCW

Online consulting18926505116


Product details

 Distribution line image monitoring device

model:DX-WPS100-HGCW

1、 Demand analysis

As a channel to transport electric energy, outdoor overhead transmission lines have been operating at high loads. Because the external environment of the lines is complex and changeable, they are also the direct victims of natural environmental impact and man-made damage. There are often potential power supply safety hazards such as disconnection and tower tilt. Under the proposal of the construction of "safe smart grid", it is essential to strengthen the whole process supervision of environmental hazards in transmission channels. The power distribution line image monitoring device launched by our company is a system designed mainly for the monitoring of transmission lines against external broken tower foundations, severe ice disaster weather, tower cranes at the construction site, and vehicles crossing overhead lines.


2、 Working principle

The visual image monitoring device of the transmission line channel uses the 4G/CDMA/GPRS technology of the operator to regularly take high-definition images and alarm pictures of the monitoring station and upload them to the monitoring center and the relevant personnel's mobile WeChat. The monitoring center can capture the images of the front station as required, and know the monitoring site conditions at any time through the returned pictures; It can also enable the visual image monitoring device of transmission line channel to send pictures to the monitoring center at a certain time every day, so as to realize the image monitoring of front-end transmission line against external damage.

The equipment is equipped with front view camera, rear view camera and bottom view camera as standard, which can monitor the line channel and distribution transformer station area at the same time. The device can automatically monitor and identify hidden dangers and give early warning in time by collecting images/videos, transformer input and output temperature and other data, so as to realize the visual online monitoring function in the distribution transformer substation area. The time linkage operation and maintenance personnel can ensure effective control of hidden dangers in a short time until they are eliminated.


3、 Functional features

Multiple monitoring: front view camera, rear view camera and bottom view camera are standard configuration, which can monitor the transmission channel and substation area at the same time;


4、 Technical parameters

project

technical parameter

video camera

Industrial high-definition gun camera is used for front and rear view channel lens, and 2 million night vision full-color lens is standard, with illumination ≤ 0.001Lux

Bottom view camera is equipped with 5 megapixel wide-angle lens as standard, and the field angle is 120°

data acquisition

Automatic setting of interval time/support manual photo collection

Support real-time video, and support short video recording of more than 20s

Collection of environmental temperature and humidity data, transformer column head and three-phase line temperature data

antenna

Built in antenna

Positioning function

GPS positioning

communication mode

2G/3G/4G wireless transmission is adopted to meet the needs of China Telecom, China Unicom and China Mobile. 2G, 3G and 4G networks of three operators are supported, and operators can be selected according to site conditions

Monitoring period

The front-end analysis takes pictures every 5 minutes by default, and the regular return returns every 1 hour by default, and the sampling time period can be set freely; After the equipment is photographed, the front-end analysis shall be conducted, and the identified hidden dangers shall be returned immediately, and the hidden dangers shall be returned regularly

storage

TF card is supported, and image data shall be stored circularly for at least 30 days, and video data shall be stored circularly for at least 7 days

MTBF

≥30000 hours

Inspection and commissioning

Inspection and debugging can be carried out without dismantling the machine

Degree of protection

IP67

Equipment quality

≤2.5Kg(host)

Power supply mode

Mains power supply+spare lithium battery

Continuous power supply for single full charge of battery

≥12h

Main housing material

polycarbonate

working temperature

-25℃ - +70℃

relative humidity

5% ~ RH

atmospheric pressure

55kPa   ~ 106kPa

Design service life of the whole machine

Not less than 8 years


Contact us

Shenzhen Dingxin Smart Technology Co., Ltd
Tel:0755-21612345 Mobile:18926505116
Fax:0755-21612345 QQ:2986188Mail:dxzhkj@126.com
Address: Room 201, No. 2, Xiangyuer Industrial Park, No. 8, Longsheng Road, Longgang Community, Longgang Street, Longgang District, Shenzhen

The online monitoring, distributed fault location and cable online monitoring equipment for power transmission and distribution lines launched by SHENZHEN DINSEE SMART TECHNOLOGY CO.,LTD. has been widely used in Southern Power Grid and State Grid, and has achieved good results.

Record No.: Yue ICP Bei 2022070794-1 | Website Map XML Map